Specification Reference

BS EN 60439

(BS 5486 : Part 1)

LV Control Gear and MCC: Withstand short-circuit fault rating up to 80kA/1SEC - diversity factor 1.0 - fault containment to form 4 - fuse or circuit breaker short circuit protective device.

 

BS EN 60947

(BS 4941 : Part 1 & IEC 292)

LV Motor Starters : Dielectric testing - co-ordination of starter components, for "no damage" under short-circuit condition.

 

BS EN 60694

(BS 5227 : Part 1 & IEC 298)

AC metal enclosed and metalclad control gear, vacuum contactor starters and MCC 1kV - 11kV and vacuum circuit breakers to 12kV.

 

BS EN 60529

(BS 5420 & IEC 144)

Ingress Protection : LV and HV MCC up to IP55 and weatherproof enclosures.

Ingress Protection Codes to BS EN 60529

(IEC 144 and IEC 529)

1st Numeral

2nd Numeral

Solids Protection

Water Protection

0

Non-protected.

0

Non-protected

1

Protected against objects greater than 50mm diameter.

1

Protected against dripping water.

2

Protected against objects greater than 12mm diameter.

2

Protected against dripping water at an angle of 15 degrees.

3

Protected against objects greater than 2.5mm diameter.

3

Protected against dripping water at an angle of 60 degrees.

4

Protected against objects greater than 1mm diameter.

4

Protected against splashing water.

5

Dust protected.

5

Protected against water jets.

6

Dust tight.

6

Protected against heavy seas.

 

7

Protected against immersion.

8

Protected against submersion.

Typical Motor FLC (3ph 50Hz)

380 to 440 Volts

kW

380V

415V

440V

0.55

1.6

1.5

1.4

1.1

2.8

2.5

2.4

1.5

3.8

3.5

3.3

2.2

5.4

5.0

4.7

4

9.0

8.4

7.9

5.5

11.9

11

10.3

7.5

16.1

14.4

14

11

23

21

19.8

15

30.5

28

26.4

22

45

41

39

30

60

55

52

37

75

69

65

45

87

80

75

55

107

98

92

75

148

136

128

90

180

164

154

110

214

196

185

150

292

268

252

200

391

358

338

300

573

525

495

Typical Motor FLC (3ph 50Hz)

3.3kV to 11kV

kW

3.3kV

6.6kV

11kV

100

22

-

-

125

27

-

-

150

33

-

-

175

43

-

-

200

49

22

-

225

54

25

-

250

64

27

-

300

83

32

-

400

102

42

25

500

154

51

31

750

205

77

46

1000

257

103

62

1250

308

129

77

1500

359

154

93

1750

410

180

108

2000

-

205

124

2500

-

256

154

3000

-

309

185

4000

-

412

247

5000

-

-

309

Starter Types, Current & Torque

(For Other Types Consult Igranic)

Main Starter Types

Typical Starting Current

Typical Starting Torque

 

(% of DOL start)

(% of DOL start)

Direct on Line (DOL)

100
Typically 6 x FLC

100

Star/Delta (S/D or Y/D)

33

33

Auto-Transformer

36 (at 60% voltage tap)

36

Primary Reactor

60 (at 60% current tap)

36

Wound Rotor (Stator/Rotor)

Dependant on machine characteristic and rotor resistance