Circuit Breakers |
||
|
|
||
|
|
||
|
Circuit Breakers |
|
The Igranic 'PowerVac' range of Medium Voltage Circuit Breakers offers a versatile range of ASTA certified vacuum circuit breakers for distribution suite and feeder applications, featuring a compact fully withdrawable design and metalclad contruction. Other types of circuit breaker can be supplied if required (specified manufacturer or SF6 etc.). |
|
Ratings |
|||
|
Current (A) |
630 |
1250 |
2000 |
|
Weights: VCB/Housing (Kg) |
105/425 |
115/440 |
140/560 |
|
Width (mm) |
600 |
600 |
800 |
|
Voltage (kV) at 50Hz |
3.3, 6.6 and 12 |
||
|
Insulation Level: |
|
||
|
Impulse (kVp) |
75 or 95 option |
||
|
1-min Power Freq (kV) |
28 |
||
|
Short-Circuit Breaking Current (kA) |
20 or 25 option |
||
|
Transient Recovery Voltage (kVp) |
20.6 |
||
|
Short-Circuit Making Current (kAp) |
50 or 63 option |
||
|
Operating Sequence |
0 - 0.3sec - CO - 3min - CO |
||
|
Duration of Short Circuit (s) |
3 |
||
|
Opening Time (ms) |
35 |
||
|
Break Time |
<3 Cycles |
||
|
Closing Time at No Load (ms) |
50 |
||
|
Closing & Tripping: |
|
||
|
Voltage (V d.c.) |
30 or 110 option |
||
|
Current (A) |
6.5 3.5 |
||
|
Full Load Switching Life |
10,000 operations |
||
![]()
|
Prices and Information |
|